Trane INTELLIPAK ™ ™ ™ ™ ™ Commercial Single-Zone Rooftop Air Conditioners with CV or VAV Control User Manual

Page 34

Advertising
background image

33

Installation (Continued)

Table 3-4

Sizing Natural Gas Pipe Mains & Branches

Sizing Natural Gas Pipe Mains & Branches

Gas Input (Cubic Feet/Hour)*

Notes:
1. If more than one unit is served by

Gas Supply

1-1/4" 1-1/2"

2"

2-1/2"

3"

4"

the same main gas supply, consider

Pipe Run (ft)

Pipe

Pipe

Pipe

Pipe

Pipe

Pipe

the total gas input (cubic feet/hr.)

10

1050

1600

3050

4800

8500 17500

and the total length when determining

20

730

1100

2100

3300

5900 12000

the appropriate gas pipe size.

30

590

890

1650

2700

4700

9700

2. Obtain the Specific Gravity and

40

500

760

1450

2300

4100

8300

BTU/Cu.Ft. from the gas company.

50

440

670

1270

2000

3600

7400

3. The following example demonstrates

60

400

610

1150

1850

3250

6800

the considerations necessary when

70

370

560

1050

1700

3000

6200

determining the actual pipe size.

80

350

530

990

1600

2800

5800

90

320

490

930

1500

2600

5400

Example: A 40' pipe run is needed to

100

305

460

870

1400

2500

5100

connect a unit with a 500 MBH furnace to a

125

275

410

780

1250

2200

4500

natural gas supply having a rating of 1,000

150

250

380

710

1130

2000

4100

BTU/Cu.Ft. and a specific gravity of 0.60

175

225

350

650

1050

1850

3800

200

210

320

610

980

1700

3500

Cu.Ft/Hour = Furnace MBH Input

* Table is based on a specific gravity of 0.60. Use Table 3-1 for Gas BTU/Cu.Ft. X Multiplier (Table 3-1)
specific gravity of the local gas supply.

Cu.Ft/Hour = 500
Table 3 indicates that a 1-1/4" pipe is required.

Specific Gravity Multipliers

Specific

Gas Heating Capacity Altitude Correction Factors

Gravity

Multiplier

0.50

1.10

Sea Level 2001 2501 3501 4501 5501 6501

0.55

1.04

To 2000 To 2500 To 3500 To 4500 To 5500 To 6500 To 7500

0.60

1.00

Capacity

0.65

0.96

Multiplier 1.00 .92 .88 .84 .80 .76 .72
Note: Correction factors are per AGA Std. 221.30 - 1964, Part VI, 6.12.
Local codes may supersede.

Altitude (Ft.)

Figure 3-10

Unit Gas Trains (Natural Gas)