Table 4-6 (continued) – Trane INTELLIPAK ™ ™ ™ ™ ™ Commercial Single-Zone Rooftop Air Conditioners with CV or VAV Control User Manual

Page 93

Advertising
background image

91

Table 4-6 (Continued)

90 Ton Operating Pressure Curve (All Compressors and Condenser Fans, per ckt; "On")

COOLING CYCLE PRESSURE CURVE

(Based on Indoor Airflow of 400 CFM / Ton)

FULL LOAD

180

200

220

240

260

280

300

320

340

360

380

50

55

60

65

70

75

80

85

90

95

100

SUCTION PRESSURE, PSIG

DISCHARG

E PRESSURE, PSIG

105 F OD Ambient

95 F OD Ambient

85 F OD Ambient

75 F OD Ambient

65 F OD Ambient

To Check Operating Pressures
1. Start the unit and allow the pressures to stabilize.
2. Measure the outdoor air dry bulb temperature (F)
entering the condenser coil.
3. Measure the discharge and suction pressure (psig)
next to the compressor.

4. Plot the outdoor dry bulb temperature and the
operating suction pressure (psig) onto the chart.
5. At the point of intersection, read to the left for the
discharge pressure. The measured discharge
pressure should be within ± 7 psig of the graph.

105 Ton Standard & Hi-Cap Operating Pressure Curve (All Compressors and Condenser Fans, per ckt, "On")

COOLING CYCLE PRESSURE CURVE

(Based on Indoor Airflow of 400 CFM / Ton)

FULL LOAD

180

200

220

240

260

280

300

320

340

360

380

50

55

60

65

70

75

80

85

90

95

100

SUCTION PRESSURE, PSIG

DISCHARG

E PRESSURE, PSIG

105 F OD Ambient

95 F OD Ambient

85 F OD Ambient

75 F OD Ambient

65 F OD Ambient

To Check Operating Pressures
1. Start the unit and allow the pressures to stabilize.
2. Measure the outdoor air dry bulb temperature (F)
entering the condenser coil.
3. Measure the discharge and suction pressure (psig)
next to the compressor.

4. Plot the outdoor dry bulb temperature and the
operating suction pressure (psig) onto the chart.
5. At the point of intersection, read to the left for the
discharge pressure. The measured discharge
pressure should be within ± 7 psig of the graph.