Figure 4-2 (Continued)

40, 50 & 55 Ton Supply Fan Performance without Inlet Guide Vanes

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

6.0

6.5

7.0

7.5

8.0

0

2000

4000

6000

8000

10000 12000 14000 16000 18000 20000 22000 24000 26000 28000 30000

CFM

STATIC PRESSURE, Inc

h

e

s

w.c

.

40 HP

7.5 HP

10 HP

15 HP

20 HP

25 HP

30 HP

1200 RPM

600 RPM

700 RPM

800 RPM

900 RPM

1000 RPM

1100 RPM

500 RPM

5 HP

40% w

o

cf

m

50%

60%

70%

S_HFC40, C50, C55
Dual 20 X 20 Fans
Entrance Losses
- without Inlet Guide Vanes
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust
Fan Curve Limits
- Minimum Motor HP = 7.5
- Maximum Motor HP
C40, C50 & C55 = 30 HP
- Maximum RPM
7.5 - 15 HP = 1141
20 - 30 HP = 1170
- Maximum CFM
C40 = 18,000
C50 = 22,500
C55 = 24,000
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.

90%

80%

60, 70 & 75 Ton Supply Fan Performance without Inlet Guide Vanes

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

6.0

6.5

7.0

7.5

8.0

0

3000

6000

9000

12000

15000

18000

21000

24000

27000

30000

33000

36000

CFM

STATIC PRESSURE, Inc

h

e

s

w

.c

.

S_HFC60, C70, C75
Dual 22 X 22 Fans
Entrance Losses
- without Inlet Guide Vanes
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust
Fan Curve Limits
- Minimum Motor HP = 10
- Maximum Motor HP = 40
- Maximum RPM = 1130
- Maximum CFM
C60 = 27,000
C70 & C75 = 30,000
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.

600 RPM

40% w

o

c

fm

7.5 HP

700 RPM

800 RPM

900 RPM

1000 RPM

1100 RPM

1200 RPM

50%

70%

80%

90% wocfm

10 HP

15 HP

20 HP

25 HP

30 HP

40 HP

50 HP

500 RPM

60%