Table 4-1 (continued) – Trane INTELLIPAK ™ ™ ™ ™ ™ Commercial Single-Zone Rooftop Air Conditioners with CV or VAV Control User Manual

Page 64

Advertising
background image

62

Table 4-1 (Continued)

Service Test Guide for Component Operation

COMPONENT

COMPONENT CONFIGURATION

Occ

BEING TESTED

Supply Exhaust Condenser Heat Stages

Compressor Stage

Econo Exhaust

VFD

Unocc

(Cont.)

Fan

Fan

Fans

1

2

3

1

2

3

4

Damper Damper

IGV

Output Relay

** CONDENSER FANS

90 Ton

1A-2B3/2B14

Off

Off

1A-On/1B-Off Off Off Off K11-Off K3-Off K12-On K4-Off Closed

Closed Closed

0%

Default

2A-Off/2B-Off

1B-2B1/2B2

Off

Off

1A-Off/1B-On Off Off Off K11-On K3-Off K12-Off K4-Off Closed

Closed Closed

0%

Default

2A-Off/2B-Off

2A-2B6/2B13

Off

Off

1A-Off/1B-Off Off Off Off K11-Off K3-Off K12-Off K4-On Closed

Closed Closed

0%

Default

2A-On/2B-Off

2B-2B4/2B5

Off

Off

1A-Off/1B-Off Off Off Off K11-Off K3-On K12-Off K4-Off Closed

Closed Closed

0%

Default

2A-Off/2B-On

105 & 115 Ton

1A-2B3/2B14

Off

Off

1A-On/1B-Off Off Off Off K11-Off K3-Off K12-On K4-Off Closed

Closed Closed

0%

Default

2A-Off/2B-Off

1B-2B1/2B2/2B19

Off

Off

1A-Off/1B-On Off Off Off K11-On K3-Off K12-Off K4-Off Closed

Closed Closed

0%

Default

2A-Off/2B-Off

2A-2B6/2B13

Off

Off

1A-Off/1B-Off Off Off Off K11-Off K3-Off K12-Off K4-On Closed

Closed Closed

0%

Default

2A-On/2B-Off

2B-2B4/2B5/2B15

Off

Off

1A-Off/1B-Off Off Off Off K11-Off K3-On K12-Off K4-Off Closed

Closed Closed

0%

Default

2A-Off/2B-On

130 Ton

1A-2B3/2B14

Off

Off

1A-On/1B-Off Off Off Off

Off

Off

Off

Off

Closed

Closed Closed

0%

Default

2A-Off/2B-Off

1B-2B1/2B2

Off

Off

1A-Off/1B-On Off Off Off

Off

Off

Off

Off

Closed

Closed Closed

0%

Default

2B19/2B20

2A-Off/2B-Off

2A-2B6/2B13

Off

Off

1A-Off/1B-Off Off Off Off

Off

Off

Off

Off

Closed

Closed Closed

0%

Default

2A-On/2B-Off

2B-2B4/2B5

Off

Off

1A-Off/1B-Off Off Off Off

Off

Off

Off

Off

Closed

Closed Closed

0%

Default

2B15/2B21

2A-Off/2B-On

SUPPLY FAN

On

Off

All Off

Off Off Off

Off

Off

Off

Off

Closed

Closed

100%

100% Unocc

Open

EXHAUST FAN

Off

On

All Off

Off Off Off

Off

Off

Off

Off

Closed

100%

100%

100% Default

Open

Open

GAS HEAT (Full Cap.)

On

Off

All Off

On On N/A

Off

Off

Off

Off

Closed

Closed

100%

100% Unocc

Open

Stage 1

On

Off

All Off

On Off N/A

Off

Off

Off

Off

Closed

Closed

100%

100% Unocc

Open

Stage 2

On

Off

All Off

Off On N/A

Off

Off

Off

Off

Closed

Closed

100%

100% Unocc

Open

Full Modulating

On

Off

All Off

90% Select

Off

Off

Off

Off

Closed

Closed

100%

100%

Unocc

(High Fire Adjustment)

Open

Full Modulating

On

Off

All Off

5% Select

Off

Off

Off

Off

Closed

Closed

100%

100%

Unocc

(Low Fire Adjustment)

Open

Limited Modulating

On

Off

All Off

90% Select

Off

Off

Off

Off

Closed

Closed

100%

100%

Unocc

(High Fire Adjustment)

Open

Limited Modulating

On

Off

All Off

33% Select

Off

Off

Off

Off

Closed

Closed

100%

100%

Unocc

(Low Fire Adjustment)

Open

ELECTRIC HEAT

On

Off

All Off

On On On

Off

Off

Off

Off

Closed

Closed

100%

100% Unocc

Open

Stage 1

On

Off

All Off

On Off Off

Off

Off

Off

Off

Closed

Closed

100%

100% Unocc

Open

Stage 2

On

Off

All Off

Off On Off

Off

Off

Off

Off

Closed

Closed

100%

100% Unocc

Open

Stage 3

On

Off

All Off

Off Off On

Off

Off

Off

Off

Closed

Closed

100%

100% Unocc

Open

Hydronic Heat

Off

Off

All Off

100% Select

Off

Off

Off

Off

Closed

Closed Closed

0%

Default

Pre - Heater

Off

Off

All Off

On N/A N/A

Off

Off

Off

Off

Closed

Closed Closed

0%

Default

Fresh Air Dampers

Off

Off

All Off

Off Off Off

Off

Off

Off

Off

100%

Closed Closed

0%

Default

Open

Exhaust Dampers

Off

Off

All Off

Off Off Off

Off

Off

Off

Off

100%

100%

Closed

0%

Default

Open

* - Compressors for the 20 thru 60 Ton units can operate individually or together and in any order while in the SERVICE TEST mode.
Compressors 1A &1B and compressors 2A & 2B operate simultaneously within their respective circuits on the 70 thru 105 Ton units.
Compressors 1A & 1B, 1C & 1D, 2A & 2B, 2C & 2D operate simultaneously within their respective circuits on 115 and 130 Ton units.
Caution: Do Not operate the compressors for extended periods of time without the condenser fans, High Head Pressure will develope.
** - Condenser fan outputs can operate individually or together and in any order while in the SERVICE TEST mode.
*** - Once the unit has started, refer to the Status Menu in the Human Interface for the OA CFM.
**** - RTM OCC/UNOCC output in the Service Test Mode must be in the unoccupied mode to open the system VAV boxes and the
Inlet Guide Vanes or to drive the VFD to 100%.