02_NVspec_ver202e_pdf.xls 4_Network Variables

3n

Request mode

network input SNVT_hvac_mode nviMode_n;

This input network variable is used to change the operation mode of the indoor unit.
This nv is not required to use when setting the operation mode only from the local side such as the
local remote controller.

Valid Range

HVAC_AUTO:0 = Auto mode

HVAC_HEAT:1 = Heat mode

HVAC_COOL:3 = Cool mode

HVAC_PRE_COOL:5 = Dry mode

HVAC_FAN_ONLY:9 = Fan mode

:Else = Fan mode

*The range of mode setting differs depending on the model of the indoor and outdoor units.

Default Value

The default value is determined by the state of the air conditioner (indoor unit).
This variable becomes value = 0 until the value is updated after the power supply of LM-AP.

4n

Mode state

network output SNVT_hvac_mode nvoMode_n;

This output network variable indicates the present mode of the indoor unit.

Valid Range

HVAC_AUTO:0 = Auto mode
HVAC_HEAT:1 = Heat mode
HVAC_COOL:3 = Cool mode
HVAC_PRE_COOL:5 = Dry mode
HVAC_FAN_ONLY:9 = Fan mode
HVAC_NULL:0xFF = Value not available
*The value is 0 while LM-AP is initialized.

When Transmitted

This output network variable is transmitted promptly as the state changes.
This variable is also transmitted as the state changes by the operation from the local such as the local
remote controller.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM-AP.

Update Rate

Update Rate

Update Rate

Update Rate

The value defined by nciSndHrtBt_1 (Send Heartbeat_1) is valid.

Default Service Type

Acknowledged

WLN01-1023(Ver2.02)