Request local prohibit setpoint, Local prohibit setpoint state – MITSUBISHI ELECTRIC LMAP-02E User Manual

Page 18

Advertising
background image

02_NVspec_ver202e_pdf.xls 4_Network Variables

23n

Request Local Prohibit SetPoint

network input SNVT_switch nviProSetP_n;

This input network variable is used to prohibit the temperature setpoint change of the
local remote controller connected to the indoor unit.

Valid Range

value field : not used

state field : 0 = Permit temperature setpoint change for local remote controller

state field : 1 = Prohibit temperature setpoint change for local remote controller

: Else = Permit temperature setpoint change for local remote controller

Default Value

The default value permit temperature setpoint change for local remote controller.
This variable becomes value = 0 until the value is updated after the power supply of LM-AP.

NOTE: For the use of this function, turn ON the switch(SW1-1) on LM-AP.(Factory setting "OFF")

24n

Local Prohibit SetPoint state

network output SNVT_switch nvoProSetP_n;

This output network variable indicates the prohibit/permit of the temperature setting for
the local remote controller connected to the indoor unit or ventilator.

Valid Range

value field : not used = 0 constantly

state field : 0 = Permit temperature setpoint change for local remote controller

state field : 1 = Prohibit temperature setpoint change for local remote controller
*The value is 0 while LM-AP is initialized.

When Transmitted

This output network variable is transmitted promptly as the state changes.

Update Rate

Update Rate

Update Rate

Update Rate

The maximum update rate is not available.

Default Service Type

Acknowledged

NOTE: For the use of this function, turn ON the switch (SW1-1) on LM-AP.(Factory setting "OFF")

WLN01-1023(Ver2.02)

- 18 -