02_NVspec_ver202e_pdf.xls 5_Configuration

(7)

Send Heartbeat Start Time

network input config SNVT_time_sec nciStartHrtBt

This configuration property defines the start time of automatic updating at the powering of the LM-AP.
The objective network configurations are given below.
 ・nciSndHrtBt_1(Send Heartbeat_1)
 ・nciSndHrtBt_2(Send Heartrbeat_2)

Valid Range

The valid range covers from 0.0,1200.0 to 6540.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds results in 1800.0 seconds.
The setting to 0.1 ~ 1199.9 seconds results in 1200.0 seconds.
The setting to 6540.1 ~ 6553.4 seconds results in 6540.0 seconds.

Default Value

6553.5 seconds (judged as 1800 seconds)

(8)

Send Start Time

network input config SNVT_time_sec nciStartOutTm

This configuration property defines the start time of the output network variable change at powering of
LM-AP.
The objective network variables are given below.

 ・nvoOnOff_n(On/Off Run State )
 ・nvoMode_n(Mode State)
 ・nvoLCMode_n(LOSSNAY Mode State)
 ・nvoSetPoint_n(Setpoint State)
 ・nvoFanSpeed_n(Fan Speed State)
 ・nvoThermo_n(Thermostat On/Off State )
 ・nvoSpaceTemp_n(Indoor Temperature State )
 ・nvoAlarm_n(Alarm State)
 ・nvoProOnOff_n(Local Prohibit On/Off State)
 ・nvoProMode_n(Local Prohibit Mode State)
 ・nvoProSetP_n(Local Prohibit SetPoint State )

Valid Range

The valid range covers from 0.0,1200.0 to 6540.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds results in 1800.0 seconds.
The setting to 0.1 ~ 1199.9 seconds results in 1200.0 seconds.
The setting to 6540.1 ~ 6553.4 seconds results in 6540.0 seconds.

Default Value

6553.5 seconds (judged as 1800 seconds)

WLN01-1023(Ver2.02)

- 23 -