Minimum send time, Initialize start time – MITSUBISHI ELECTRIC LMAP-02E User Manual

Page 21

Advertising
background image

02_NVspec_ver202e_pdf.xls 5_Configuration

(3)

Minimum Send Time

network input config SNVT_time_sec nciMinOutTm;

This configuration property defines the minimum send time between the output network variables.
The objective network variables are given below.
 ・nvoOnOff_n(On/Off Run State )
 ・nvoMode_n(Mode State)
 ・nvoLCMode_n(LOSSNAY Mode State)
 ・nvoSetPoint_n(Setpoint State)
 ・nvoFanSpeed_n(Fan Speed State)
 ・nvoThermo_n(Thermostat On/Off State )
 ・nvoSpaceTemp_n(Indoor Temperature State )
 ・nvoAlarm_n(Alarm State)
 ・nvoProOnOff_n(Local Prohibit On/Off State)
 ・nvoProMode_n(Local Prohibit Mode State)
 ・nvoProSetP_n(Local Prohibit SetPoint State )

Valid Range

The valid range covers from 0,1.0 to 600.0 seconds (per 1 second).
The setting to 0.0 or 6553.5 seconds makes the minimum send time setting invalid.
The setting to 0.1 ~ 0.9 seconds results in 1.0 second.
The setting to 600.1 ~ 6553.4 seconds results in 600.0 seconds.

Default Value

6553.5 seconds (Setting invalid)

(4)

Initialize Start Time

network input config SNVT_time_sec nciInitStartTm

This configuration property defines the starting time of the output network variables at the initial output.
The objective network variables are given below.
 ・nvoOnOff_n(On/Off Run State )
 ・nvoMode_n(Mode State)
 ・nvoLCMode_n(LOSSNAY Mode State)
 ・nvoSetPoint_n(Setpoint State)
 ・nvoFanSpeed_n(Fan Speed State)

Valid Range

The valid range covers from 0.0,900.0 to 3600.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds makes the initial output time setting invalid.
The setting to 0.1 ~ 899.9 seconds results in 900.0 seconds.
The setting to 3600.1 ~ 6553.4 seconds results in 3600.0 seconds.

Default Value

6553.5 seconds (Setting invalid)

WLN01-1023(Ver2.02)

- 21 -