02_NVspec_ver202e_pdf.xls 5_Configuration

(5)

Initialize Send Time_1

network input config SNVT_time_sec nciInitOutTm_1

This configuration property defines the minimum send time between the output network variables at initial
output.
This configuration is valid when setting the Initialize Start Time to other values than 0.0 second.
The objective network variables are given below.

 ・nvoOnOff_n(On/Off Run State )
 ・nvoMode_n(Mode State)
 ・nvoLCMode_n(LOSSNAY Mode State)
 ・nvoSetPoint_n(Setpoint State)
 ・nvoFanSpeed_n(Fan Speed State)

Valid Range

The valid range covers from 0.0,0.1 to 1.0 second (per 100m seconds).
The setting to 0.0 or 6553.5 seconds makes the initial output minimum send time setting invalid.
The setting to 1.1 ~ 6553.4 seconds results in 1.0 second.

Default Value

6553.5 seconds (Setting invalid)

(6)

Initialize Send Time_2

network input config SNVT_time_sec nciInitOutTm_2

This configuration property defines the minimum send time between each unit of the indoor, Mr.SLIM and
ventilator at the initial output.
This configuration is valid when setting the Initialize Start Time to other values than 0.0 second.
The objective network variables are given below.
 ・nvoOnOff_n(On/Off Run State )
 ・nvoMode_n(Mode State)
 ・nvoLCMode_n(LOSSNAY Mode State)
 ・nvoSetPoint_n(Setpoint State)
 ・nvoFanSpeed_n(Fan Speed State)

Valid Range

The valid range covers from 0.0,5.1 to 50.0 second (per 1second).
The setting to 0.0 or 6553.5 seconds makes the initial output minimum send time setting invalid.
The setting to 0.1 ~ 4.9 seconds results in 5.0 seconds.
The setting to 50.1 ~ 6553.4 seconds results in 50.0 seconds.

Default Value

6553.5 seconds (Setting invalid)

WLN01-1023(Ver2.02)

- 22 -