Request local prohibit mode, Local prohibit mode state – MITSUBISHI ELECTRIC LMAP-02E User Manual

Page 17

Advertising
background image

02_NVspec_ver202e_pdf.xls 4_Network Variables

21n

Request Local Prohibit mode

network input SNVT_switch nviProMode_n;

This input network variable is used to prohibit the mode change operation of the
local remote controller connected to the indoor unit.

Valid Range

value field : not used

state field : 0 = Permit mode change operation of local remote controller

state field : 1 = Prohibit mode change operation of local remote controller

: Else = Permit mode change operation of local remote controller

Default Value

The default value permit mode change operation of local remote controller.
This variable becomes value = 0 until the value is updated after the power supply of LM-AP.

NOTE: For the use of this function, turn ON the switch(SW1-1) on LM-AP.(Factory setting "OFF")

22n

Local Prohibit mode state

network output SNVT_switch nvoProMode_n;

This output network variable indicates the prohibit/permit state of the On/Off operation
of the local remote controller connected to the ventilator.

Valid Range

value field : not used = 0 constantly

state field : 0 = Permit mode change operation of local remote controller

state field : 1 = Prohibit mode change operation of local remote controller
*The value is 0 while LM-AP is initialized.

When Transmitted

This output network variable is transmitted promptly as the state changes.

Update Rate

Update Rate

Update Rate

Update Rate

The maximum update rate is not available.

Default Service Type

Acknowledged

NOTE: For the use of this function, turn ON the switch (SW1-1) on LM-AP.(Factory setting "OFF")

WLN01-1023(Ver2.02)

- 17 -