Request lossnay mode, Lossnay mode state – MITSUBISHI ELECTRIC LMAP-02E User Manual

Page 11

Advertising
background image

02_NVspec_ver202e_pdf.xls 4_Network Variables

13n

Request LOSSNAY Mode

network input SNVT_switch nviLCMode_n;

This input network variable is used to change the operation mode of the ventilator
(at independent operation without interlocking) .
This nv is not required to use when setting the operation mode only from the local side such as the
local remote controller. remote controller.

Valid Range

state field : 0 & value field : 0%    = LOSSNAY ventilation

state field : 0 & value field : Else = Bypass ventilation

state field : 1 & value field : not care = Damper auto

state field : Else = Damper auto

Default Value

The default value is determined by the state of the ventilator.
This variable becomes value = 0 until the value is updated after the power supply of LM-AP.

14n

LOSSNAY Mode state

network output SNVT_switch nvoLCMode_n;

This output network variable indicates the present operation mode of the ventilator.

Valid Range

value field : 0% =LOSSNAY ventilation

value field : 100%   = Bypass ventilation

state field : not used =0 constantly
*The value is 0 while LM-AP is initialized.

When Transmitted

This output network variable is transmitted promptly when the state changes.
It is also transmitted as the state changes by the operation from the local such as the local remote
controller.
This variable is output by the ncilnitStartTm (Initialize Start Time) at the powering of LM-AP.

Update Rate

Update Rate

Update Rate

Update Rate

The value defined by nciSndHrtBt_1 (Send Heartbeat_1) and nciMinOutTm (Minimum Send Time) is valid.

Default Service Type

Acknowledged

WLN01-1023(Ver2.02)

- 11 -