York PREDATOR BP 090 User Manual

Page 14

Advertising
background image

259336-YTG-B-0606

14

Unitary Products Group

TABLE 8: HEATING APPLICATION DATA 7 1/2 TON HP HEAT (METRIC)

M

3

S

ID DB

(C)

KW

OUTDOOR TEMPERATURE (C)

-23

-18

-12

-7

-1

4

10

16

1.06

12.8

Capacity

7.7

9.3

11.3

13.8

16.8

20.5

24.9

30.4

Power Input

4.4

4.7

4.9

5.1

5.4

5.6

5.8

6.1

21.1

Capacity

6.6

8.3

10.3

12.8

15.8

19.4

23.9

29.3

Power Input

5.2

5.4

5.7

5.9

6.1

6.4

6.6

6.9

26.7

Capacity

5.5

7.2

9.2

11.7

14.7

18.3

22.8

28.3

Power Input

5.6

5.8

6.1

6.3

6.5

6.8

7.0

7.2

1.42

12.8

Capacity

8.6

10.2

12.2

14.7

17.7

21.4

25.8

31.3

Power Input

4.3

4.6

4.8

5.0

5.3

5.5

5.8

6.0

21.1

Capacity

7.6

9.2

11.2

13.7

16.7

20.4

24.8

30.3

Power Input

5.1

5.3

5.6

5.8

6.1

6.3

6.5

6.8

26.7

Capacity

6.5

8.1

10.1

12.6

15.6

19.3

23.7

29.2

Power Input

5.5

5.7

6.0

6.2

6.4

6.7

6.9

7.2

1.77

12.8

Capacity

10.0

11.6

13.6

16.1

19.1

22.8

27.2

32.7

Power Input

4.5

4.7

4.9

5.2

5.4

5.6

5.9

6.1

21.1

Capacity

8.9

10.6

12.6

15.1

18.1

21.7

26.2

31.7

Power Input

5.2

5.5

5.7

5.9

6.2

6.4

6.7

6.9

26.7

Capacity

7.8

9.5

11.5

14.0

17.0

20.6

25.1

30.6

Power Input

5.6

5.9

6.1

6.3

6.6

6.8

7.0

7.3

THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.
FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (kW)

Advertising