TABLE 9: HEATING APPLICATION DATA 10 TON HP HEAT (IMPERIAL)

CFM

ID DB

CAP & kW

OUTDOOR TEMPERATURE (°F) (72% RH)

-10

0

10

20

30

40

50

60

3000

55

MBH

21.2

34.2

47.3

60.3

73.3

86.4

99.4

112.4

KW

6.0

6.4

6.8

7.1

7.5

7.9

8.3

8.6

70

MBH

28.9

42.0

55.0

68.0

81.0

94.1

107.1

120.1

KW

7.4

7.8

8.1

8.5

8.9

9.2

9.6

10.0

80

MBH

30.0

43.0

56.1

69.1

82.1

95.2

108.2

121.2

KW

8.3

8.7

9.0

9.4

9.8

10.1

10.5

10.9

4000

55

MBH

23.8

36.8

49.8

62.9

75.9

88.9

102.0

115.0

KW

5.5

5.9

6.2

6.6

7.0

7.4

7.7

8.1

70

MBH

31.3

44.3

57.3

70.3

83.4

96.4

109.4

122.5

KW

6.8

7.1

7.5

7.9

8.3

8.6

9.0

9.4

80

MBH

32.6

45.6

58.7

71.7

84.7

97.8

110.8

123.8

KW

7.8

8.1

8.5

8.9

9.2

9.6

10.0

10.4

5000

55

MBH

22.7

35.8

48.8

61.8

74.9

87.9

100.9

113.9

KW

5.0

5.4

5.7

6.1

6.5

6.8

7.2

7.6

70

MBH

30.5

43.5

56.5

69.6

82.6

95.6

108.6

121.7

KW

6.3

6.7

7.1

7.5

7.8

8.2

8.6

8.9

80

MBH

31.5

44.6

57.6

70.6

83.7

96.7

109.7

122.8

KW

7.2

7.6

8.0

8.3

8.7

9.1

9.5

9.8

THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.
FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (MBH = 3.415 x KW)