TABLE 10: HEATING APPLICATION DATA 10 TON HP HEAT (METRIC)

M

3

S

ID DB

(C)

KW

OUTDOOR TEMPERATURE (C)

-23

-18

-12

-7

-1

4

10

16

1.42

12.8

Capacity

6.2

10.0

13.8

17.7

21.5

25.3

29.1

32.9

Power Input

6.0

6.4

6.8

7.1

7.5

7.9

8.3

8.6

21.1

Capacity

8.5

12.3

16.1

19.9

23.7

27.6

31.4

35.2

Power Input

7.4

7.8

8.1

8.5

8.9

9.2

9.6

10.0

26.7

Capacity

8.8

12.6

16.4

20.2

24.1

27.9

31.7

35.5

Power Input

8.3

8.7

9.0

9.4

9.8

10.1

10.5

10.9

1.89

12.8

Capacity

7.0

10.8

14.6

18.4

22.2

26.1

29.9

33.7

Power Input

5.5

5.9

6.2

6.6

7.0

7.4

7.7

8.1

21.1

Capacity

9.2

13.0

16.8

20.6

24.4

28.2

32.1

35.9

Power Input

6.8

7.1

7.5

7.9

8.3

8.6

9.0

9.4

26.7

Capacity

9.6

13.4

17.2

21.0

24.8

28.6

32.5

36.3

Power Input

7.8

8.1

8.5

8.9

9.2

9.6

10.0

10.4

2.36

12.8

Capacity

6.7

10.5

14.3

18.1

21.9

25.8

29.6

33.4

Power Input

5.0

5.4

5.7

6.1

6.5

6.8

7.2

7.6

21.1

Capacity

8.9

12.7

16.6

20.4

24.2

28.0

31.8

35.7

Power Input

6.3

6.7

7.1

7.5

7.8

8.2

8.6

8.9

26.7

Capacity

9.2

13.1

16.9

20.7

24.5

28.3

32.1

36.0

Power Input

7.2

7.6

8.0

8.3

8.7

9.1

9.5

9.8