Table 12: electrical data - 10 ton hp, Table 13: unit voltage limitations, Table 14: electric heat multipliers – York PREDATOR BP 090 User Manual

Page 17

Advertising
background image

259336-YTG-B-0606

Unitary Products Group

17

NOTES FOR TABLES 15 THROUGH 30:

Blower performance includes dry coil and 2” throwaway
filters.

ESP (External Static Pressure) given is that available for the
supply and return air duct system. All internal resistances
have been deducted from the total static pressure of the
blower.

NOTE:

Electric heaters are rated at nominal voltage. Use
this table to determine the electric heat capacity for
heaters supplied at lower voltages.

TABLE 11: ELECTRICAL DATA - 7-1/2 TON HP

Voltage

Compressors

OD

Fan

Motors

Supply Air

BLower

Motor FLA

Pwr

Exh

Motor Electric Heater

Model No.

Actual

Kw

Heater
Amps

Minimum Circuit

Ampacity (Amps)

MCA

with Power

Exhaust

(Amps)

Max Fuse

Size

*

(Amps)

Max Fuse Size

w/Pwr. Exh.*

(Amps)

RLA

ea

LRA

ea

FLA

ea

1.5 HP

(1.1 kW)

2 HP

(1.5 kW)

FLA

1.5 HP

(1.1 kW)

2 HP

(1.5 kW)

1.5 HP

(1.1 kW)

2 HP

(1.5 kW)

1.5 HP

(1.1 kW)

2 HP

(1.5 kW)

1.5 HP

(1.1 kW)

2 HP

(1.5 kW)

380

8.3

62

1.1

4.3

5.2

2.2

None

-

-

25.2

26.1

27.4

28.3

30

30

35

35

2TP04520950

5.6

8.5

35.8

36.7

38.0

38.9

40

40

40

45

2TP04521850

11.3

17.2

46.6

47.5

48.8

49.7

50

50

50

50

2TP04522450

15.0

22.8

53.7

54.6

55.9

56.8

60

60

60

60

2TP04523650

21.3

32.4

65.6

66.5

67.8

68.7

70

70

70

70

415

8.3

62

1.1

4.3

5.2

2.2

None

-

-

25.2

26.1

27.4

28.3

30

30

35

35

2TP04520950

6.7

9.3

36.8

37.7

39.0

39.9

40

40

40

45

2TP04521850

13.5

18.8

48.7

49.6

50.9

51.8

50

50

60

60

2TP04522450

17.9

24.9

56.3

57.2

58.5

59.4

60

60

60

60

2TP04523650

25.4

35.3

69.3

70.2

71.5

72.4

70

80

80

80

*

Maximum HACR breaker of the same amp size is acceptable.

TABLE 12: ELECTRICAL DATA - 10 TON HP

Voltage

Compressors

OD

Fan

Motors

Supply Air

BLower

Motor FLA

Pwr

Exh

Motor Electric Heater

Model No.

Actual

Kw

Heater
Amps

Minimum Circuit

Ampacity (Amps)

MCA

with Power

Exhaust

(Amps)

Max Fuse

Size

*

(Amps)

Max Fuse Size

w/Pwr. Exh.*

(Amps)

RLA

ea

LRA

ea

FLA

ea

2 HP

(1.5 kW)

4HP

(3 kW)

FLA

2 HP

(1.5 kW)

4 HP

(3 kW)

2 HP

(1.5 kW)

4 HP

(3 kW)

2 HP

(1.5 kW)

4 HP

(3 kW)

2 HP

(1.5 kW)

4 HP

(3 kW)

380

8.1

73.0

1.1

5.2

7.5

2.2

None

--

--

25.6

27.9

27.8

30.1

30

35

35

35

2TP04521850

11.3

17.2

47.1

49.4

49.3

51.6

50

50

50

60

2TP04522450

15.0

22.8

54.1

56.4

56.3

58.6

60

60

60

60

2TP04523650

21.3

32.4

66.1

68.4

68.3

70.6

70

70

70

80

2HP04535450

33.8

51.4

70.7

73.6

73.4

76.3

80

80

80

80

415

8.1

73.0

1.1

5.2

7.5

2.2

None

--

--

25.6

27.9

27.8

30.1

30

35

35

35

2TP04521850

13.5

18.8

49.1

51.4

51.3

53.6

50

60

60

60

2TP04522450

17.9

24.9

56.8

59.1

59.0

61.3

60

60

60

70

2TP04523650

25.4

35.3

69.8

72.1

72.0

74.3

70

80

80

80

2HP04535450

40.4

56.2

76.8

79.6

79.5

82.4

80

80

80

90

*

Maximum HACR breaker of the same amp size is acceptable.

Only 25.4 kW of electric heat can be simultaneously energized with the mechanical heating. The full 40.4 kW operates only if both compressors are locked out.

TABLE 13: UNIT VOLTAGE LIMITATIONS

POWER RATING

MIN.

MAX.

380/415-3-50

342

456

TABLE 14: ELECTRIC HEAT MULTIPLIERS

NOMINAL VOLTAGE

RATING

kW CAP. MULTIPLIER

380

440

0.627

415

440

0.75

Advertising