TABLE 1: PHYSICAL DATA

COMPONENT

MODELS

090

120

Evaporator

Blower

Blower, Centrifugal Dia. X Wd. in. (Dia. X Wd. mm)

15 x 15 (381 x 381)

15 x 15 (381 x 381)

Motor, Standard HP (kW)

1-1/2 (1.1)

2 (1.5)

Motor, Optional HP (kW)

2 (1.5)

4 (3)

Evaporator Coil

Rows

3

4

Fins per Inch (2.54 cm.)

15

15

Height in. (mm)

40 (1020)

40 (1020)

Face Area ft.

2

each (m

2

)

13.2 (1.23)

13.2 (1.23)

Condenser Fan

(2 per Unit)

Propeller Dia. in., each (mm)

24 (610)

24 (610)

Motor HP, each (kW)

3/4 (.56)

3/4 (.56)

CFM, Nominal (each)

4000

4000

Condenser Coil

(2 per unit)

Rows (each)

1

2

Fins per Inch (2.54 cm)

20

20

Height in., each (mm)

44 (1120)

44 (1120)

Face Area ft.

2

each (mm)

14.5 (1.35)

14.5 (1.35)

Refrigerant

Charge

System 1 lb./oz. (kg)

9 lbs. 4 oz. (4.20)

15 lbs. 4 oz. (6.92)

System 2 lb./oz. (kg)

9 lbs. 0 oz. (4.06)

15 lbs. 0 oz. (6.80)

Compressors

Quantity

2

2

Type

Recip

Scroll

Air Filters

Size Wd. x Ht. x Thickness in.

(Wd. x Ht x Thickness mm)

25x20x2

(635 x 508 x 51)

25x20x2

(635 x 508 x 51)

Number Per Unit

4

4

TABLE 2: BP CAPACITY RATINGS

SIZE

(TONS)

COOLING CAPACITY ARI RATINGS

*

CFM

HEATING CAPACITY

SOUND

RATING

(dB)

NOM ELEC

HEAT CAP

(kW)

MBH

EER

IPLV

MBH @

47° F

COP @

47°F

MBH @

17°F

COP @

17°F

7-1/2
(090)

93

9.1

7.5

3000

86

3.1

44

2.0

84

9, 18, 24 34

10

(120)

120

9.4

9.4

4000

116

3.15

75

2.25

85

18, 24, 34 54

*

Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.

Rated in accordance with ARI 270 standard.

See Table 14.