VEGA Conductive electrodes User Manual

Page 12

Advertising
background image

12

Conductive measuring system

Measuring data input (channel)

Number

1 (1 x level detection or
1 x pump control -Min-Max)

Response resistance

1 … 200 kOhm adjustable

Parallel resistance
- for fault monitoring

220 kOhm

Meas. circuit

max. 5 V eff, max. 1 mA

Permissible line capacitance

1 x 100 nF or
2 x 70 nF at Min-Max.-control

Switching hysteresis

approx. 15 %

Measuring data input, Ex-technical data

Signal circuit

in classification intrinsic safety EEx ia IIC

Max. values
- U

O

10,6 V

- I

K

8 mA

- P

20 mW

Characteristics

linear

Inner effective inductance

negligible

Inner effective capacitance

negligible

Max. permissible outer inductance

5 mH

Max. permissible outer capacitance

570 nF

The intrinsically safe circuits are reliably galvanically isolated from the not-intrinsically safe
circuits up to a peak value of the nominal voltage of 375 V.

Relay outputs

Number

1

Mode

overfill protection (A) and dry run protection (B)
changeable

Contact

1 spdt per output

Contact material

AgCdO and Au plated

Turn-on voltage

min. 10 mV
max. 250 V AC or 250 V DC

Switching current

min. 10 µA
max. 3 A AC or 1 A DC

Breaking capacity

max. 750 VA or 54 W

Transistor outputs

Number

1 (synchronuously switching with relay outputs)

Galvanic isolation

floating

Turn-on voltage

U

B

= max. 36 V DC

Switching current

I

B

= max. 60 mA

Voltage loss on transistor

U

CE

= approx. 1,5 V at I

B

= 60 mA

Blocking current

I

O

< 10 µA

Integration time

Adjustable

0,2 … 20 s