VEGA Conductive electrodes User Manual

Page 9

Advertising
background image

Conductive measuring system

9

Product description

Ambient conditions

Permissible operating temperature

-20°C … +50°C

Storage and transport temperature

-40°C … +70°C

Electrical protective measures

Protection

IP 20

Protection class

II

Electrical connection

Screw terminal

max. for 1,5 mm

2

CE-conformity

VEGATOR 256C signal conditioning instrument meets the protective regulations of EMVG
(89/336/EWG) and NSR (72/23/EWG). The conformity has been judged acc. to the following
standards:
EMVG Emission

EN 50 081 - 1

Susceptibility

EN 50 082 - 2

NSR

EN 61 010 - 1

Signal conditioning instrument VEGATOR 532 Ex

General

Series

19"-module card, multipoint connector acc. to
DIN 41 612 incl. transparent cover

Dimensions

B = 25,4 mm (5 TE), H = 128,4 mm, D = 162 mm

Weight

approx. 170 g

Power supply

Operating voltage

20 … 53 V AC, 50/60 Hz
20 … 72 V DC

Power consumption

max. 2 W, 3 VA

Fuse
- supply range

T 1 A, 250 V

- switching power

min. 35 A at 250 V AC or 125 V DC

Measuring data input (channel)

Number

2 (2 x level detection or
2 x pump control -Min-Max)

Response resistor

1 … 200 kOhm adjustable

Parallel resistor
- for fault monitoring

220 kOhm

Meas. circuit

max. 5 V eff, max. 1 mA

Permissible line capacitance

1 x 100 nF or
2 x 70 nF with Min-Max.-control

Switching hysteresis

approx. 15 %

Advertising