Switch point adjustment – VEGA Conductive electrodes User Manual

Page 34

Advertising
background image

34

Conductive measuring system

Set-up VEGATOR 631 Ex

1

2

3

1

2

3

Mode B

preferably as dry run protection

means with covered max.-electrode
- relay energizes, connection 12 - 14 is

connected through relay

- transistor output is conductive
- LED output lights

means with uncovered max.-electrode (level
detection) or min.-electrode (pump control)
- relay deenergizes, connection 12 - 13 is

connected through relay

- transistor output blocks
- LED output extinguishes

Switch point adjustment

Level detection for max.-signal

Pre-requirements
- Set the selection switch (13) to mode A
- Connect the signal conditioning instrument

to power supply

- Turn the potentiometer (2) to position 0

Switch point max.-signal

- Fill the vessel until the max. electrode is

covered by approx. 1 cm

- Turn the potentiometer (2) slowly clockwise

until the yellow LED extinguishes

The max. electrode is now adapted to the
product conductivity, i.e. the relay
deenergizes at max. level and the transistor
blocks.

Level detection for min.-signal

Pre-requirements
- Set the selection switch (13) to mode B
- Connect the signal conditioning instrument

to power supply

- Turn the potentiometer (2) to position 10

Switch point min.-signal

- Empty the vessel until the min. electrode is

covered by approx. 1 cm

- Turn the potentiometer (2) slowly

anticlockwise until the yellow LED
extinguishes

The min. electrode is now adapted to the
product conductivity, i.e. the relay
deenergizes at min. level and the transistor
blocks.

Advertising