5 Connecting to voltage supply

5.1 Preparing the connection

Generally not the following safety instructions:

l

Connect only in the complete absence of line voltage

l

If overvoltage surges are expected, overvoltage arresters

should be installed

Tip:

We recommend VEGA overvoltage arresters FS-LB-I and ÜSB

62-36G.X.

In hazardous areas you should take note of the appropriate

regulations, conformity and type approval certificates of the

sensors and power supply units.

If reliable separation is required, power supply with mains

voltage and current output are transmitted via separate two-

wire connection cables. The supply voltage range can differ

depending on the instrument version. The exact range is

stated in the "Technical data" in the "Supplement".
This instrument is designed in protection class I. To maintain

this protection class, it is absolutely necessary that the ground

conductor be connected to the internal ground terminal. Take

note of the general installation regulations.
As a rule, connect VEGASON 66 to vessel ground (potential

euqalisation) or in case of plastic vessels to the next ground

potential. For this purpose, there is a ground terminal on the

side of the instrument housing.
For power supply, an approved installation cable with PE

conductor is necessary.
The 4 … 20 mA current output is connected with standard two-

wire cable without screen. If strong electromagnetic interfer-

ence is expected, screened cable should be used.
An outer cable diameter of 5 … 9 mm ensures the seal effect

of the respective cable entry.
If screened cable is necessary, connect the cable screen on

both ends to ground potential. In the sensor, the screen must

be connected directly to the internal ground terminal. The

ground terminal on the outside of the housing must be

connected to the potential equalisation (low impedance).

Note safety instructions

Take note of safety

instructions for Ex

applications

Select power supply

Selecting the connection ca-

ble

Cable screening and ground-

ing