VEGA VEGASON 66 4 … 20 mA_HART four-wire User Manual

Page 34

Advertising
background image

vessel wall (with solids). To adapt the sensor to these different

conditions, you should first select in this menu item "Liquid" or

"Solid".

Medium

Liquid

With solids, you can also choose between "Powder/Dust",

"Granular/Pellets" or "Ballast/Pebbels".
Through this additional selection, the sensor is adapted

perfectly to the product and measurement reliability, partic-

ularly in products with bad reflective properties, is considerably

increased.
Enter the requested parameter via the appropriate keys, save

your settings and jump to the next menu item with the [->] key.
Apart from the medium, the vessel shape can also influence

the measurement. To adapt the sensor to these measuring

conditions, this menu item offers different options depending

on whether liquid or solid is selected. With "Liquid" these are

"Storage tank", "Stilling tube", "Open vessel" or "Stirred

vessel", with "Solid", "Silo" or "Bunker".

Vessel form

Storage tank

Enter the requested parameter via the appropriate keys, save

your settings and jump to the next menu item with the [->] key.
To suppress fluctuations in the measured value display, e.g.

by fluctuating product surfaces, an integration time can be set.

This time can be between 0 and 999 seconds. Keep in mind

that also the reaction time of the complete measurement will

be bigger and the sensor will react on measured value

changes with a delay. In general a time of a few seconds will

be sufficient to smooth the measured value display.

Damping

0 s

Vessel form

Damping

Setup with the indicating and adjustment module PLICSCOM

34

VEGASON 66 - 4 ... 20 mA/HART - four-wire

28783

-EN

-060731

Advertising