Basic adjustment

Display

Diagnostics

Service

Info

2 Select the menu item "Basic adjustment" with [->] and

confirm with [OK]. Now the menu item "Min. adjustment" is

displayed.

Min. adjustment

0.00 %

=

5.000 m(d)

4.000 m(d)

3 Prepare the % value for editing with [OK] and set the

cursor to the requested position with [->]. Set the

requested percentage value with [+] and save with [OK].

The cursor jumps now to the distance value.

4 Enter the appropriate distance value in m (corresponding

to the percentage value) for the empty vessel (e.g. distance

from the sensor to the vessel bottom).

5 Save the settings with [OK] and move to "Max. adjustment"

with [->].

Proceed as follows:

Max. adjustment

100.00 %

=

1.000 m(d)

2.000 m(d)

1 Prepare the % value for editing with [OK] and set the

cursor to the requested position with [->]. Set the

requested percentage value with [+] and save with [OK].

The cursor jumps now to the distance value.

2 Enter the appropriate distance value in m (corresponding

to the percentage value) for the full vessel. Keep in mind

that the max. level must lie below the dead band.

3 Save the settings with [OK] and move to "Medium

selection" with [->].

Each product has different reflective properties. In addition,

there are various interfering factors which have to be taken into

account: agitated product surfaces and foam generation (with

liquids); dust generation, material cones and echoes from the

Carry out max. adjustment

Medium selection

Setup with the indicating and adjustment module PLICSCOM

VEGASON 66 - 4 ... 20 mA/HART - four-wire