Fig. 5: Position of the spacer

1

Spacer

Note:
Measurement in a standpipe is not recommended for very adhesive
products.

If there is a danger of the probe touching the vessel wall during
operation due to product movements or agitators etc., the measuring
probe should be securely fixed.

In the gravity weight there is a thread (M12), e.g. for a ring bolt
(optional) - (article no. 2.27424).

Make sure that the probe cable is not completely taut. Avoid tensile
loads on the cable.

Avoid undefined cable-vessel connections, i.e. the connection must be
either grounded reliably or isolated reliably. Any deviation from this
requirement can lead to measurement errors.

VEGAFLEX

66 should be integrated in the vessel insulation. This

prevents the electronics from strong heating or cooling by temperature
radiation.

Make sure that with heated or cooled vessels the permissible ambient
temperature on the housing is not exceeded. The permissible ambient
temperature is stated in chapter "Technical data" under "Ambient
conditions
".

Fixing

Temperature insulation

VEGAFLEX

66 • Profibus PA

15

4 Mounting