VEGA VEGAFLEX 66 (-20…+250°C) Profibus PA User Manual

Page 57

Advertising
background image

l

Free Place

Byte-No.

1

2

3

4

5

Status

Status

(FB1)

IEEE-754-

Floating point value

PA-OUT

(FB1)

Format

Value

Data format of the output signal

Byte4

Byte3

Byte2 Byte1 Byte0

Status

Value (IEEE-754)

Fig. 30: Data format of the output signal

The status byte corresponds to profile 3.0 "Profibus PA Profile for Process Control Devices" coded.
The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 … 0 = 0).

The measured value is transferred as a 32 bit floating point number in the IEEE-754 format.

Byte n

Byte n+1

Bit

7

VZ

Exponent

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Bit

7
2

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Sign

Bit

Significant

7

6

5

4

3

2

1

0

-1

-2

-3

-4

-5

-6

-7

Byte n+2

Byte n+3

Bit

7
2

Significant

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Bit

7
2

Bit

6
2

Bit

5
2

Bit

4
2

Bit

3
2

Bit

2
2

Bit

1
2

Bit

0
2

Significant

-9

-10 -11 -12 -13 -14 -15 -16 -17

-18 -19

-20 -21 -22 -23

-8

Value = (-1)

VZ

2

(Exponent - 127)

(1 + Significant)

Fig. 31: Data format of the measured value

Coding of the status byte associated with the PA output value

Status
code

Description according to Pro-
fibus standard

Possible cause

0x00

bad - non-specific

Flash-Update active

0x04

bad - configuration error

l Adjustment error
l Configuration error with PV-Scale (PV-Span too small)
l Unit irregularity
l Error in the linearization table

VEGAFLEX

66 • Profibus PA

57