VEGA VEGAFLEX 66 (-20…+250°C) Profibus PA User Manual

Page 30

Advertising
background image

Gating out of false signals

Change now?

Proceed as follows:

1

Move from the measured value display to the main menu by
pushing [OK].

2

Select the menu item "Service" with [->] and confirm with [OK].
Now the menu item "False signal suppression" is displayed.

3

Confirm "False signal suppression - Change now" with [OK] and
select in the below menu "Create new". Enter the actual distance
from the sensor to the product surface. All false signals in this area
are detected by the sensor and saved after confirming with [OK].

Note:
Check the distance to the product surface, because if an incorrect (too
large) value is entered, the existing level will be saved as false signal.
The filling level would then no longer be detectable in this area.

This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".

The following data are read out or written with this function:

l

Measured value presentation

l

Adjustment

l

Medium

l

Vessel form

l

Damping

l

Linearisation curve

l

Sensor-TAG

l

Displayed value

l

Unit of measurement

l

Language

l

Sensitivity

l

PA scaling unit

l

PV-Out-Scale

l

Channel

l

Additional PA value

The following safety-relevant data are not read out or written:

l

Sensor address

l

PIN

l

Sensor length/Sensor type

l

Gating out of false signals

Copy sensor data

30

VEGAFLEX

66 • Profibus PA

6 Set up with the indicating and adjustment module PLICSCOM

34171

-EN

-100427

Advertising