VEGA VEGAFLEX 66 (-20…+250°C) Profibus PA User Manual

Page 58

Advertising
background image

Status
code

Description according to Pro-
fibus standard

Possible cause

0x0C

bad - sensor failure

l Hardware error
l Converter error
l Leakage pulse error
l Trigger error

0x10

bad - sensor failure

l Measured value generation error

0x1f

bad - out of service constant

"O

ut of Service" mode switched on

0x44

uncertain - last unstable value

Failsafe replacement value (Failsafe-Mode = "Last value" and
already valid measured value since switching on)

0x48

uncertain substitute set

l Switch on simulation
l Failsafe replacement value (Failsafe-Mode = "Fsafe value")

0x4c

uncertain - initial value

Failsafe replacement value (Failsafe-Mode = "Last valid value" and
no valid measured value since switching on)

0x51

uncertain - sensor; conversion
not accurate - low limited

Sensor value < lower limit

0x52

uncertain - sensor; conversion
not accurate - high limited

Sensor value > upper limit

0x80

good (non-cascade) - OK

OK

0x84

good (non-cascade) - active
block alarm

Static revision (FB, TB) changed (10 sec. active, after the parameter
of the static category was written)

0x89

good (non-cascade) - active ad-
visory alarm - low limited

Lo-Alarm

0x8a

good (non-cascade) - active ad-
visory alarm - high limited

Hi-Alarm

0x8d

good (non-cascade) - active cri-
tical alarm - low limited

Lo-Lo-Alarm

0x8e

good (non-cascade) - active cri-
tical alarm - high limited

Hi-Hi-Alarm

58

VEGAFLEX

66 • Profibus PA

10 Supplement