VEGA VEGAFLEX 66 (-20…+250°C) Profibus PA User Manual

Page 31

Advertising
background image

Copy sensor data

Copy sensor data?

Basic adjustment
If the function "Reset" is carried out, the sensor resets the values of the
following menu items to the reset values (see chart):

2)

The following values will be reset:

Function

Reset value

Max. adjustment

Distance, upper dead zone

Min. adjustment

Distance, supplied sensor length

Min. adjustment - Cable version

Distance, lower dead zone

Damping ti

0 s

Linearisation

linear

Sensor-TAG

Sensor

Display

PA-Out 1

Channel (PV)

lin %

Additional PA value (PV)

lin %

Out-Scale-Unit

%

PV-Out-Scale

0.00 lin % = 0.0 %
100.0 lin % = 100 %

The values of the following menu items are not reset to the reset
values (see chart) with "Reset":

Function

Reset value

Sensor address

No reset

Language

No reset

Factory setting
Like basic adjustment, in addition, special parameters are reset to
default values.

3)

Pointer
The min. and max. distance values are reset to the actual value.

2)

Sensor-specific basic adjustment.

3)

Special parameters are parameters which are set customer-specifically on
the service level with the adjustment software PACTware.

Reset

VEGAFLEX

66 • Profibus PA

31

6 Set up with the indicating and adjustment module PLICSCOM

34171

-

EN

-100427