VEGA VEGAFLEX 62 Profibus PA User Manual
Page 16
Advertising
If possible, avoid sockets. Mount the sensor flush with the vessel top. If
this is not possible, use short sockets with small diameter.
Higher sockets or sockets with a bigger diameter can generally be
used. They simply increase the upper dead band. Check if this is
relevant for your measurement.
In such cases, always carry out a gating out of false signals after
installation. You can find further information under "Setup procedure".
h
d
d
h
DN40 ... DN150
£ 150
> DN150 ... DN200
£ 100
Fig. 8: Mounting socket
When welding the socket, make sure that the socket is flush to the
vessel wall.
1
2
Fig. 9: Socket must be installed flush
1
Unfavourable installation
2
Socket flush - optimum installation
Socket
16
VEGAFLEX
62 • Profibus PA
4 Mounting
31839
-EN
-100426