Status
code

Description according to Pro-
fibus standard

Possible cause

0x48

uncertain substitute set

l Switch on simulation
l Failsafe replacement value (Failsafe-Mode = "Fsafe value")

0x4c

uncertain - initial value

Failsafe replacement value (Failsafe-Mode = "Last valid value" and
no valid measured value since switching on)

0x51

uncertain - sensor; conversion
not accurate - low limited

Sensor value < lower limit

0x52

uncertain - sensor; conversion
not accurate - high limited

Sensor value > upper limit

VEGAFLEX