VEGA VEGAFLEX 62 Profibus PA User Manual
Page 57
Advertising
Status
code
Description according to Pro-
fibus standard
Possible cause
0x48
uncertain substitute set
l Switch on simulation
l Failsafe replacement value (Failsafe-Mode = "Fsafe value")
0x4c
uncertain - initial value
Failsafe replacement value (Failsafe-Mode = "Last valid value" and
no valid measured value since switching on)
0x51
uncertain - sensor; conversion
not accurate - low limited
Sensor value < lower limit
0x52
uncertain - sensor; conversion
not accurate - high limited
Sensor value > upper limit