VEGA VEGAFLEX 62 Profibus PA User Manual

Page 31

Advertising
background image

Linearisation curve

linear

Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.

Caution:
Note the following, if VEGAFLEX 62 is used as part of an overfill
protection system according to WHG:

If a linearisation curve is selected, the measuring signal is no longer
compulsorily linear proportional to the level. This must be taken into
consideration by the user, particularly when adjusting the switching
point on the level switch.

In this menu item you can enter an unambiguous designation for the
sensor, e.g. the measurement loop name or the tank or product
designation. In digital systems and in the documentation of larger
plants, a singular designation should be entered for exact identification
of individual measuring points.

Sensor-TAG

Sensor

With this menu item, the Basic adjustment is finished and you can now
jump to the main menu with the [ESC] key.

High sockets or vessel installations, such as e. g. struts or agitators as
well as buildup and weld joints on the vessel walls, cause interfering
reflections which can impair the measurement. A false echo storage
detects and marks these false echoes, so that they are no longer taken
into account for the level measurement. A false echo memory should
be created with low level so that all potential interfering reflections can
be detected.

Gating out of false signals

Change now?

Proceed as follows:

1

Move from the measured value display to the main menu by
pushing [OK].

Sensor-TAG

Gating out of false sig-
nals

VEGAFLEX

62 • Profibus PA

31

6 Set up with the indicating and adjustment module PLICSCOM

31839

-

EN

-100426