2 profibus pa – data format and status byte, 2 profibus pa - data format and status byte – VEGA VEGAFLEX 62 Profibus PA User Manual

Page 56

Advertising
background image

10.2 Profibus PA - Data format and status byte

Data format of the output signal

Byte4

Byte3

Byte2

Byte1 Byte0

Status

Value (IEEE-754)

Fig. 33: Data format of the output signal

Status byte:

The status byte corresponds to profile 3.0 "Profibus PA Profile for Process Control Devices" coded.
The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 … 0 = 0).

Measured value (Value):

The measured value is transferred as a 32 bit floating point number in the IEEE-754 format.

Byte n

Byte n+1

Bit

7

VZ

Exponent

Bit

6

2

Bit

5

2

Bit

4

2

Bit

3

2

Bit

2

2

Bit

1

2

Bit

0

2

Bit

7

2

Bit

6

2

Bit

5

2

Bit

4

2

Bit

3

2

Bit

2

2

Bit

1

2

Bit

0

2

Sign

Bit

Significant

7

6

5

4

3

2

1

0

-1

-2

-3

-4

-5

-6

-7

Byte n+2

Byte n+3

Bit

7

2

Significant

Bit

6

2

Bit

5

2

Bit

4

2

Bit

3

2

Bit

2

2

Bit

1

2

Bit

0

2

Bit

7

2

Bit

6

2

Bit

5

2

Bit

4

2

Bit

3

2

Bit

2

2

Bit

1

2

Bit

0

2

Significant

-9

-10

-11

-12

-13

-14

-15

-16

-17

-18

-19

-20

-21

-22

-23

-8

Value = (-1)

VZ

2

(Exponent - 127)

(1 + Significant)

Fig. 34: Data format of the measured value

Coding of the status byte associated with the PA output value

Status
code

Description according to Pro-
fibus standard

Possible cause

0x00

bad - non-specific

Flash-Update active

0x04

bad - configuration error

l Adjustment error
l Configuration error with PV-Scale (PV-Span too small)
l Unit irregularity
l Error in the linearization table

0x0C

bad - sensor failure

l Hardware error
l Converter error
l Leakage pulse error
l Trigger error

0x10

bad - sensor failure

l Measured value generation error
l Temperature measurement error

0x1f

bad - out of service constant

"O

ut of Service" mode switched on

0x44

uncertain - last unstable value

Failsafe replacement value (Failsafe-Mode = "Last value" and
already valid measured value since switching on)

56

VEGAFLEX

62 • Profibus PA

10 Supplement

31839

-EN

-100426