VEGA VEGAFLEX 62 Profibus PA User Manual

Page 49

Advertising
background image

Current value

10 mA, ±0.5 mA

Damping (63 % of the input variable)

0 … 999 s, adjustable

Fulfilled NAMUR recommendations

NE

43

Resolution, digital

>

1 mm (0.039 in)

Accuracy (similar to DIN EN 60770-1)

Process reference conditions according to DIN EN 61298-1

-

Temperature

+

18 … +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

+

860 … +1060 mbar/+86 … +106 kPa

(+12.5 … +15.4 psig)

Installation reference conditions

-

Min. distance to installations

>

500 mm (19.69 in)

-

Vessel

metallic, ø 1 m (3.281 ft), centric installation,
process fitting flush with the vessel ceiling

-

Medium

Water/Oil (Dk value ~2.0)

-

Installation

Probe end does not touch the vessel bottom

Sensor parameter adjustment

Gating out of false signals carried out
In bulk solids applications, implementing a false
signal suppression is generally not recommended.
The accuracy of bulk solid applications depends
considerably on the application. Hard and fast
accuracy specifications are thus not available.

Deviation

see diagrams
Depending on the installation conditions, there can
be deviations which can be rectified with an
adaptation of the adjustment or a change of the
measured value offset in the DTM service mode.

VEGAFLEX

62 • Profibus PA

49

10 Supplement

31839

-

EN

-100426

Advertising