4 mounting, 1 general instructions, 4mounting – VEGA VEGAWELL 52 4 … 20 mA_HART Pt 100 User Manual

Page 11

Advertising
background image

4

Mounting

4

.1 General instructions

M

ake sure that all parts of the instrument exposed to the process, in

particular the sensor element, process seal and process fitting, are
suitable for the existing process conditions. These include above all
the process pressure, process temperature as well as the chemical
properties of the medium.

Y

ou can find the specifications in chapter "Technical data" or on the

type label.

L

ateral movements of the transmitter can cause measurement errors.

F

or this reason, mount the instrument in a calm area or in a suitable

protective tube.

T

he connection cable has a capillary for atmospheric pressure

compensation. Therefore lead the cable end into a dry environment or
a suitable terminal housing, for example VEGABOX 02 or VEGA-
DIS

62.

Fig. 3: Mounting example: VEGAWELL 52 in a pump shaft with breather housing
VEGABOX 02

Suitability for the pro-
cess conditions

Mounting position

Pressure compensation

Mounting example

VEGAWELL

52 • 4 … 20

mA/HART Pt

11

4 M

ounting

35402

-

EN

-111021

Advertising