VEGA VEGAWELL 52 4 … 20 mA_HART Pt 100 User Manual

Page 33

Advertising
background image

Nominal range

Overload capacity, max.
pressure

Overload capacity, min.
pressure

0 … 70

psi

900

psi

0

psi

0 … 150

psi

1300

psi

0

psi

0 … 350

psi

1900

psi

0

psi

Output variable

O

utput signal

4 … 20

mA/HART

S

ignal resolution

1 µA

F

ault signal

<

3.6

mA; 20.5 mA; 22 mA; unchanged (adjustable

via PACTware)

M

ax. output current

22

mA

R

un-up time approx.

15

s

S

tep response time

200

ms (ti: 0 s, 0 … 63 %)

HART

output value according to HART 5.0

-

PV (P

rimary Value)

P

ressure

Additional output parameter - temperature

integrated resistance thermometer

P

t 100 according to DIN EN 60751

R

ange

-50 … +100 °C (-58 … +212 °F)

R

esolution

1 °K

A

djustment external temperature transmitter

in VEGABOX 02

4 … 20

mA/HART according to -20 … +80 °C

(-4 … +176 °F)

Reference conditions and actuating variables (similar to DIN EN 60770-1)

R

eference conditions according to DIN EN 61298-1

-

T

emperature

+

15 … +25 °C (+59 … +77 °F)

-

R

elative humidity

45 … 75 %

-

A

ir pressure

860 … 1060

mbar/86 … 106 kPa (12.5 … 15.4 psi)

D

etermination of characteristics

L

imit point adjustment according to IEC 61298-2

C

haracterstic curve

L

inear

R

eference installation position

upright, diaphragm points downward

I

nfluence of the installation position

<

0.2

mbar/20 Pa (0.003 psig)

Deviation determined according to the limit point method according to IEC 60770

7

)

A

pplies to digital HART interface as well as to analogue current output 4 … 20 mA. Specifications

refer to the set span. Turn down (TD) is the relation nominal measuring range/set span.

D

eviation with version < 0.2 %

-

T

urn down 1 : 1 up to 5 : 1

<

0.2 %

7)

I

ncl. non-linearity, hysteresis and non-repeatability.

VEGAWELL

52 • 4 … 20

mA/HART Pt

33

10 S

upplement

35402

-

EN