5 connecting to power supply, 1 preparing the connection, 5connecting to power supply – VEGA VEGAWELL 52 4 … 20 mA_HART Pt 100 User Manual

Page 15

Advertising
background image

5

Connecting to power supply

5

.1 Preparing the connection

G

enerally connect the instrument only in the complete absence of line

voltage.

T

he instrument is equipped with an integrated overvoltage protection.

F

or additional protection of the signal circuit, we recommend further

external overvoltage arresters:

l

T

ype B63-48 (use with VEGAWELL 52 with plastic housing) or

l

T

ype ÜSB 62-36G.X (use in a separate housing)

I

n hazardous areas you must take note of the respective regulations,

conformity and type approval certificates of the sensors and power
supply units.

P

ower supply and current signal are carried on the same two-wire

cable. The voltage supply range can differ depending on the
instrument version.

T

he data for power supply are specified in chapter "Technical data".

P

rovide a reliable separation between the supply circuit and the mains

circuits according to DIN VDE 0106 part 101.

VEGA

power supply units VEGATRENN 149AEx, VEGASTAB 690,

VEGADIS

371

as well as all VEGAMETs meet this requirement. When

using one of these instruments, protection class III is ensured for
VEGAWELL

52.

K

eep in mind the following additional factors that influence the

operating voltage:

l

O

utput voltage of the power supply unit can be lower under

nominal load (with a sensor current of 20.5 mA or 22 mA in case of
fault message)

l

I

nfluence of additional instruments in the circuit (see load values in

chapter "Technical data")

T

he instrument is connected with standard two-wire cable without

screen. If electromagnetic interference is expected which is above the
test values of EN 61326 for industrial areas, screened cable should be
used.

U

se cable with round cross-section. A cable outer diameter of 5 … 9 mm

(0.2 … 0.35

in) ensures the seal effect of the cable gland. If you are

using cable with a different diameter or cross-section, exchange the
seal or use a suitable cable gland.

W

e generally recommend the use of screened cable for HART

multidrop mode.

Safety instructions

Take note of sa-
fety instructions
for Ex applica-
tions
Select power supply

Select connection cable

VEGAWELL

52 • 4 … 20

mA/HART Pt

15

5 C

onnecting to power supply

35402

-

EN

-111021

Advertising