VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART four-wire Approval according to LPR radio standard User Manual

Page 21

Advertising
background image

0 %

100 %

1

2

5

4

3

6

Fig. 14: Configuration bypass

1

Radar sensor

2

Marking of the polarisation plane

3

Instrument flange

4

Distance sensor reference plane to upper tube connection

5

Distance of the tube connections

6

Ball valve with complete opening

Instructions for orientation:

l

Note marking of the polarisation plane on the sensor

l

With threaded fitting, the marking is on the hexagon, with flange
connection between the two flange holes

l

The marking must show to the direction of the tube connections to
the vessel

Instructions for the measurement:

l

The 100 % point must not be above the upper tube connection to
the vessel

l

The 0 % point must not be below the lower tube connection to the
vessel

l

Min. distance sensor reference plane to the upper edge upper
tube connection > 300 mm

l

For the parameter adjustment, select "Application standpipe" and
enter the tube diameter to compensate errors due to running time
shift

l

A false signal suppression with integrated sensor is recommended
but not mandatory

l

The measurement through a ball valve with complete run is
possible

VEGAPULS

62 • Approval according to LPR radio standard

21

4 Mounting

41719

-EN

-120301

Advertising