The real product level during this adjustment is not important, because
the min./max. adjustment is always carried out without changing the
product level. These settings can be made ahead of time without the
instrument having to be installed.

Proceed as follows:

1

Select the menu item "Setup" with [->] and confirm with [OK]. Now
select with [->] the menu item "Min. adjustment" and confirm with
[OK]

.

2

Edit the percentage value with [OK] and set the cursor to the
requested position with [->].

3

Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.

4

Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.

5

Save settings with [OK] and move with [ESC] and [->] to the max.
adjustment.

Proceed as follows:

1

Select with [->] the menu item max. adjustment and confirm with
[OK]

.

2

Prepare the percentage value for editing with [OK] and set the
cursor to the requested position with [->].

Setup/Min. adjustment

Setup/Max. adjustment

40

VEGAPULS

62 • Approval according to LPR radio standard

6 Set up with the indicating and adjustment module