Input variable

Measured variable

The measured quantity is the distance between
process fitting of the sensor and product surface.
The reference plane is the seal surface on the
hexagon or the lower side of the flange.

3

4

2

1

Fig. 43: Data of the input variable

1

Reference plane

2

Measured variable, max. measuring range

3

Antenna length

4

Useful measuring range

Max. measuring range

35 m (114.83 ft)

Output variable

Output signals

4 … 20 mA/HART - active; 4 … 20 mA/HART -
passive

Terminal voltage passive

9 … 30 V DC

Shortcircuit protection

Available

Potential separation

Available

Signal resolution

0.3 µA

Failure signal current output (adjustable)

mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA

Max. output current

22 mA

Starting current

3.6 mA

Load (4 … 20 mA/HART - active)

<

500 Ω

Damping (63 % of the input variable)

0 … 999 s, adjustable

HART output values

-

PV (Primary Value)

Distance to the level

-

SV (Secondary Value)

Level as percentage value

VEGAPULS

62 • Approval according to LPR radio standard

65

11 Supplement

41719

-EN

-120301