VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART four-wire Approval according to LPR radio standard User Manual

Page 57

Advertising
background image

Error

Cause

Rectification

Current signal
greater than 22 mA
or less than
3.6 mA

l Electronics

module in the
sensor defecti-
ve

l Exchange the instrument or send it

in for repair

The below tables show typical examples of application-relevant
measurement errors with liquids. The measurement errors are
differentiated according to the following:

l

Constant level

l

Filling

l

Emptying

The images in column "Error pattern" show the actual level with a
broken line and the level displayed by the sensor as a continuous line.

1

2

L

e

ve

l

time

0

1

Real level

2

Level displayed by the sensor

Instructions:

l

Wherever the sensor displays a constant value, the reason could
also be the fault setting of the current output to "Hold value"

l

In case of a too low level indication, the reason could be a line
resistance that is too high

Measurement error with constant level

Fault description

Error pattern

Cause

Rectification

1. Measured value
shows a too low or too
high level

Level

time

0

l Min./max. adjustment not cor-

rect

l Adapt min./max. adjustment

l Linearization curve incorrect

l Adapt linearization curve

l Installation in a bypass tube or

standpipe, hence running time
error (small measurement er-
ror close to 100 %/large error
close to 0 %)

l Check parameter "Application"

with respect to vessel form,
adapt if necessary (bypass,
standpipe, diameter)

Treatment of measure-
ment errors with liquids

VEGAPULS

62 • Approval according to LPR radio standard

57

9 Diagnosis, Asset Management and service

41719

-EN

-120301