2 adjustment – VEGA VEGAMIP R62 Receiving unit - Relay User Manual

Page 30

Advertising
background image

With the mode switch (max./min.) you can change the switching status
of the relay. You can set the required mode according to the "Function
chart
" (max. - maximum detection or overflow protection, min. -
minimum detection or dry run protection).

With these keys (7 and 8) you can adjust the switching point to the
medium.

Depending on the process, the sensitivity of VEGAMIP 62 must be set
higher or lower.

Pressing the "<--" key makes the sensor more sensitive. Pressing the
"

-->" key makes the sensor less sensitive.

You can also adjust the switching delay with the two keys.

By means of the LED indicating board, you can see the actual
receiving level during adjustment.

When the indication moves to the right, the instrument will be more
insensitive, to the left more sensitive.

6

.2 Adjustment

The microwave barrier can only be adjusted when being uncovered.
Make sure that there is no measured medium or vessel installations
between the emitting and receiving unit.

Select the requested mode (min./max.) according to the function chart.

The following function chart provides an overview of the switching
statuses depending on the set mode and level.

Level

Switching status

Signal lamp - Re-
lay (yellow)

Mode max.
Overflow protection

5

3

4

(8)

(6)

(7)

Relay energized

Mode max.
Overflow protection

5

3

4

(8)

(6)

(7)

Relay deenergized

Mode min.
Dry run protection

5

3

4

(8)

(6)

(7)

Relay energized

Mode switch (1)

Sensitivity adjustment
(7, 8)

LED indication strip -
receiving level (9)

Prerequisites

Mode

30

VEGAMIP R

62 • - Relay