VEGA VEGAFLEX 81 Foundation Fieldbus Coax probe User Manual

Page 3

Advertising
background image

3

Quick start

VEGAFLEX 81 • Foundation Fieldbus

44215-EN-130910

horizontal cylindrical or spherical tank. Activate the appropriate

curve.

5. A "False signal suppression" detects, marks and saves the false

signals so that they are no longer taken into account for level

measurement. We generally recommend a false signal suppres-

sion.

The sensor measures the distance from the sensor (reference plane)

to the product surface.

4

5

3

1

2

4

5

3

1

2

Fig. 2: Measuring ranges - VEGAFLEX 81
1 Reference plane

2 Probe length L

3 Measuring range (default setting refers to the measuring range in water)

4 Upper dead band (in this area no measurement is possible)

5 Lower dead band (in this area no measurement is possible)

For this adjustment, the distance is entered when the vessel is full

and nearly empty. If these values are not known, an adjustment with

other distances, for example, 10 % and 90 % is also possible. Starting

point for these distance specifications is always the seal surface of

the thread or flange.
1. In the menu "Additional settings", menu item "Damping" you can

adjust the requested damping of the output signal.

2. Select the parameter of the current output and the output charac-

teristics in the menu item "Current output".

Parameterization example

Further steps

Advertising