VEGA VEGAFLEX 81 Foundation Fieldbus Coax probe User Manual

Page 35

Advertising
background image

35

6 Set up with the display and adjustment module

VEGAFLEX 81 • Foundation Fieldbus

44215-EN-130910

If you have selected "No", you can enter the adjustment for the inter-

face measurement separately.

Enter the respective distance value in m for the empty vessel cor-

responding to the percentage value.

The following circumstances cause interfering reflections and can

influence the measurement:

High sockets

Vessel installations such as struts

Note:

A false signal suppression detects, marks and saves these false

signals so that they are no longer taken into account for the level and

interface measurement. We generally recommend carrying out a false

signal suppression to achieve the best possible accuracy. This should

be done with the lowest possible level so that all potential interfering

reflections can be detected.
Proceed as follows:

Enter the actual distance from the sensor to the product surface.

All interfering signals in this section are detected by the sensor and

stored.
Note:

Check the distance to the product surface, because if an incorrect

(too large) value is entered, the existing level will be saved as a false

echo. The filling level would then no longer be detectable in this area.
If a false signal suppression has already been created in the sensor,

the following menu window appears when selecting "False signal

suppression":

Setup - False signal sup-

pression

Advertising