6 Set up with the display and adjustment module

VEGAFLEX 81 • Foundation Fieldbus

44215-EN-130910

Dielectric con-

stant

Type of medium Examples

< 3

Hydrocarbons

Solvents, oils, liquid gas

This menu item is only available, if you have chosen interface meas-

urement under the menu item "Application". In this menu item you can

enter if there is a superimposed gas phase in your application.
Only set the function to "Yes", if the gas phase is permanently pre-

sent.

This menu item is only available if you have selected interface meas-

urement under the menu item "Application". In this menu item you can

choose the type of medium of the upper medium.

You can enter the dielectric constant of the upper medium directly or

have the value determined by the instrument. To do this you have to

enter the measured or known distance to the interface.

In this menu item you can enter the max. adjustment for the level. With

interface measurement this is the maximum total level.

Adjust the requested percentage value with [+] and store with [OK].

Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. The distance refers to the sensor

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.

Setup - Application - Gas

phase

Setup - Application - Di-

electric constant

Setup - Max. adjustment

Level