43

6 Set up with the display and adjustment module

VEGAFLEX 81 • Foundation Fieldbus

44215-EN-130910

Menu item

Default value

Modified value

Max. adjustment - Level

Distance: 0.000 m(d) - note block-

ing distances

Min. adjustment - Level

0 %

Min. adjustment - Level

Distance: Probe length - take dead

band into account

Accept adjustment of the level measurement?

Yes

Max. adjustment - Interface

100 %

Max. adjustment - Interface

Distance: 0.000 m(d) - note block-

ing distances

Min. adjustment - Interface

0 %

Min. adjustment - Interface

Distance: Probe length - take dead

band into account

Integration time - Level

0.0 s

Integration time - Interface

0.0 s

Linearization type

Linear

Linearization - Socket correction

0 mm

Linearization - Vessel height

Probe length

Display

Menu item

Default value

Modified value

Language

Order-specific

Displayed value 1

Filling height Level

Displayed value 2

Electronics temperature

Backlight

Switched off

Diagnostics

Menu item

Default value

Modified value

Status signals - Function control

Switched on

Status signals - Out of specification

Switched off

Status signals - Maintenance

Switched off

Device memory - Echo curve memory

Stopped

Device memory - Measured value memory

Started

Device memory - Measured value memory -

Measured values

Distance level, percentage value

level, reliability level, electronics

temperature

Device memory - Measured value memory - Re-

cording in time interval

3 min.

Device memory - Measured value memory - Re-

cording with measured value difference

15 %

Device memory - Measured value memory - Start

with measured value

Not active