9 Diagnostics and service

VEGAFLEX 81 • Foundation Fieldbus

44215-EN-130910

Code
Text mes-

sage

Cause

Rectification

S600
Unpermissi-

ble electronics

temperature

– Temperature of the pro-

cessing electronics in the

non-specified section

– Check ambient temperature

– Isolate electronics

– Use instrument with higher

temperature range

S601
Overfilling

– Level echo in the close

range not available

– Reduce level

– 100 % adjustment: Increase

value

– Check mounting socket

– Remove possible interfering

signals in the close range

– Use coaxial probe

S602
Level with-

in the search

range, com-

pensation

echo

– Compensation echo super-

imposed by medium

– 100 % adjustment: Increase

value

S603
Impermissi-

ble operating

voltage

– Operating voltage below

specified range

– Check electrical connection

– if necessary, increase

operating voltage

The following table shows the error codes and text messages in the

status message "Maintenance" and provides information on causes

as well as corrective measures.

Code
Text mes-

sage

Cause

Rectification

M500
Error in the

delivery sta-

tus

– With the reset to delivery

status, the data could not

be restored

– Repeat reset

– Load XML file with sensor

data into the sensor

M501
Error in the

non-active

linearization

table

– Hardware error EEPROM

– Exchanging the electronics

– Send instrument for repair

M502
Error in the

event memory

– Hardware error EEPROM

– Exchanging the electronics

– Send instrument for repair

M503
Reliability too

low

– Measurement certainty is

too low for a reliable meas-

urement

– Process component or

probe contaminated or

defective

– Check installation and

process conditions

– Clean or exchange process

component or probe

Maintenance