5 exchanging the electronics module, Measurement error during emptying – VEGA VEGAFLEX 81 Foundation Fieldbus Coax probe User Manual

Page 62

Advertising
background image

62

9 Diagnostics and service

VEGAFLEX 81 • Foundation Fieldbus

44215-EN-130910

Fault description

Error pattern

Cause

Rectification

4. Measured value re-

mains momentarily

unchanged during fill-

ing and then jumps to

the correct level

Level

time

0

– Turbulence on the product

surface, quick filling

– Check parameters, change if

necessary, e.g. in dosing ves-

sel, reactor

5. Measured value

jumps sporadically to

100 % during filling

Leve

l

time

0

– Changing condensation or

contamination on the probe

– Carry out a false signal sup-

pression

6. Measured value

jumps to ≥ 100 % or

0 m distance

Leve

l

time

0

– Level echo is no longer

detected in the close range

due to false signals in the close

range. The sensor goes into

overfill protection mode. The

max. level (0 m distance) as

well as the status message

"Overfill protection" are output-

ted.

– Eliminate false signals in the

close range

– Check installation conditions

– If possible, switch off the func-

tion "Overfill protection"

Measurement error during emptying

Fault description

Error pattern

Cause

Rectification

7. Measured value re-

mains unchanged in

the close range during

emptying

Level

time

0

– False echo larger than the level

echo

– Level echo too small

– Eliminate false signals in the

close range

– Remove contamination on the

probe. After having removed

the source of the false signals,

the false signal suppression

must be deleted.

– Carry out a new false signal

suppression

8. Measured value re-

mains reproducible

in one position during

emptying

Level

time

0

– Stored false signals in this

position are larger than the

level echo

– Delete false signal memory

– Carry out a new false signal

suppression

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Setup" must be carried out again or must

be checked for plausibility and completeness.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside normal working hours, seven

days a week around the clock.
Since we offer this service worldwide, the support is provided in

English. The service itself is free of charge, the only costs involved are

the normal call charges.

9.5 Exchanging the electronics module