VEGA VEGAPULS SR 68 Modbus and Levelmaster protocol User Manual

Page 17

Advertising
background image

17

4 Mounting

VEGAPULS SR 68 • Modbus and Levelmaster protocol

41371-EN-130624

1

2

Fig. 8: Position of the polarisation
1 Marking with screwed version

2 Marking with flange version

Mount the sensor at least 200 mm (7.874 in) away from the vessel

wall.

200 mm

(7.87")

Fig. 9: Mounting of the radar sensor on the vessel top

If you cannot maintain this distance, you should carry out a false

signal storage during setup. This applies particularly if buildup on the

vessel wall is expected. In such a case, it is recommended to repeat

the false signal storage at a later date with existing buildup.

Mounting should not be too close to the inflowing material as the

microwave signal will be interferred. The optimum mounting position is

on the opposite of the filling. To avoid strong pollution, the distance to

the filter or dust extraction must be as big as possible.

Installation position

Inflowing medium