VEGA VEGAPULS SR 68 Modbus and Levelmaster protocol User Manual
Page 17
17
4 Mounting
VEGAPULS SR 68 • Modbus and Levelmaster protocol
41371-EN-130624
1
2
Fig. 8: Position of the polarisation
1 Marking with screwed version
2 Marking with flange version
Mount the sensor at least 200 mm (7.874 in) away from the vessel
wall.
200 mm
(7.87")
Fig. 9: Mounting of the radar sensor on the vessel top
If you cannot maintain this distance, you should carry out a false
signal storage during setup. This applies particularly if buildup on the
vessel wall is expected. In such a case, it is recommended to repeat
the false signal storage at a later date with existing buildup.
Mounting should not be too close to the inflowing material as the
microwave signal will be interferred. The optimum mounting position is
on the opposite of the filling. To avoid strong pollution, the distance to
the filter or dust extraction must be as big as possible.
Installation position
Inflowing medium