10 Supplement

VEGAPULS SR 68 • Modbus and Levelmaster protocol

41371-EN-130624

ABB Total Flow

Wiring plan

+

+

power supply

MODBUS

D0

D1

IS GND

USB

1

2

13

45

2o

ff

on

( )

(

)

(-)

(-)

8

1

2

6

7

Bus +

Bus -

GND

VBAT

Fig. 54: Connection of VEGAPULS SR 68 to RTU ABB Total Flow
1 VEGAPULS SR 68

2 RTU ABB Total Flow

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

16 Bit Modicon

Input Register Base Number

1

The basic number of the input registers is always added to the input register address of VEGAPULS

SR 68.
Address 1303 must hence be entered as register address for 1302 for RTU ABB Total Flow.