5 levelmaster commands, Fc43 sub 14, read device identification, Parameters for the bus communication – VEGA VEGAPULS SR 68 Modbus and Levelmaster protocol User Manual

Page 77

Advertising
background image

77

10 Supplement

VEGAPULS SR 68 • Modbus and Levelmaster protocol

41371-EN-130624

Response:

Parameter

Length

Code/Data

Function Code

1 Byte

0x11

Byte Number

1 Byte

Slave ID

1 Byte

Run Indicator Status

1 Byte

FC43 Sub 14, Read Device Identification

With this function code, the Device Identification can be queried.
Request:

Parameter

Length

Code/Data

Function Code

1 Byte

0x2B

MEI Type

1 Byte

0x0E

Read Device ID Code

1 Byte

0x01 to 0x04

Object ID

1 Byte

0x00 to 0xFF

Response:

Parameter

Length

Code/Data

Function Code

1 Byte

0x2B

MEI Type

1 Byte

0x0E

Read Device ID Code

1 Byte

0x01 to 0x04

Confirmity Level

1 Byte

0x01, 0x02, 0x03, 0x81, 0x82, 0x83

More follows

1 Byte

00/FF

Next Object ID

1 Byte

Object ID number

Number of Objects

1 Byte

List of Object ID

1 Byte

List of Object length

1 Byte

List of Object value

1 Byte

Depending on the Object ID

10.5 Levelmaster commands

The VEGAPULS SR 68 is also suitable for connection to the following RTUs with Levelmaster proto-

col. The Levelmaster protocol is often called "Siemens" "Tank protocol".

RTU

Protocol

ABB Totalflow

Levelmaster

Kimray DACC 2000/3000

Levelmaster

Thermo Electron Autopilot

Levelmaster

Parameters for the bus communication

The VEGAPULS SR 68 is preset with the default values:

Advertising