5 epo connection – PowerWalker VFI 6000T LCD User Manual

Page 20

Advertising
background image

17

3) Set the external battery pack breaker in “OFF” position and

connect the 20 pieces of batteries in series.

4) Connect the external battery pack to the battery terminals.

Check the polarity of connection is correct.

5) Set the breaker of the battery pack in the “ON” position.

6) Set the mains input breaker in the “ON” position, the UPS

would power on and start to charge the battery pack.

4.5 EPO Connection

4.5.1 Introduction

Emergency power off function which the UPS supplies is, when the

emergency occurs, such as the failure of load, the UPS can cut off

the output at once by operating the EPO port manually.

4.5.2 The connection

Normally the EPO connector is opened without any connection on

the rear panel. Once the connector is closed with a wire, the UPS

would stop the output and enter EPO status.

Enable the EPO status Disable the EPO status

Fig. 4-8 Default EPO status

To recover to normal status, first EPO connector should be opened,

and enter LCD menu (illustrated in the chapter of 5.4.5) to clear

EPO status, then UPS would stop alarm and recover to Bypass

model. And UPS needs be turned on by manual operation.

The polarity of connector could be inversed by setting in LCD menu

in the chapter of 5.4.7. Contact your local distributor for further

information before modifying the settings.

Advertising